V808iCHx |
V808CHx |
| Power supply |
Rated voltage |
24 V DC |
| Permissible range of voltage |
24V DC±10% |
| Permissible momentary power failure |
Within 1ms |
| Demand (maximum rating) |
10W or less |
| Inrush current |
20A, 2ms |
| Insulation resistance |
|
500V DC, 10MΩ or more |
| Physical environment |
Operation ambient temperature |
0°C +40°C |
| Storage ambient temperature |
-10°C +60°C |
| Operation ambient humidity |
85%RH or less (without dew condensation, Max. wet bulb temperature: 39 or lower) *1 |
| Atmosphere |
Not exposed to corrosive gas or conductive dust |
| Operation altitude |
2,000 meter or lower |
| Contamination level*2 |
Level 2 |
| Mechanical |
Resistance to oscillation |
Vibration frequency: 10150Hz, acceleration: 9.8m/s2(1.0G) pulsating width: 0.075mm, X,Y,Z: 3 directions 1 hour each way |
| Resistance to shock |
Pulse shape: half-sine, peak acceleration: 147m/s2(15G), X,Y,Z: 3 directions, six times each way |
| Electric |
Noise proof |
1500Vp-p (pulse width 1 s, pulse rise time : 1ns) |
| Static discharge |
Complies with IEC61000-4-2, contact: 6kV, air: 8kV |
| Installation conditions |
Grounding |
Grounding resistance : Less than 100 Ω, FG/SG separation |
| Structure |
Protection Structure (front panel):IP65-compliant (with interface cover, CF card interface cover, and LAN cover) |
| Cooling system |
Natural air cooling |
| Weight |
Approx.1.2kg |
| Dimensions W×H×D(mm) |
259.0×232.0×55.0(without the emergency stop switch) |
| Case color |
|
Black |
| Material |
|
PC/ABS |
|
| |
V808iCHx |
V808CHx |
| Display specifications |
Screen memory |
12.5MB |
4.5MB |
| Display device |
TFT color LCD |
| Resolution W:H(dots) |
640×480 |
| Display size |
7.5 inches |
| Colors |
65,536 colors (without blinks)/ 32,768 colors (with blinks) |
| Backlight |
CCFL |
| Backlight Auto OFF |
Lit in normal (Set by the user) |
| Power lamp |
Lit in normal condition, blinks in alarm condition such as blowout of backlight bulbs |
| Contrast adjustment |
Fixed |
| Brilliance control |
Fixed |
| Number of characters |
1/4 size |
80 columns × 60 lines |
| 1-byte |
80 columns × 30 lines |
| 2-byte |
40 columns × 30 lines |
| Enlargement of characters |
|
X: 18 times Y: 18 times |
| Touch switch |
Switch resolution |
Analog: 1,024×1,024 |
| Mechanical life |
1 million times or more |
| Surface treatment |
Hard coating, Non glare finish 5% |
| Function switch |
Number of function switches |
12 switches(4 switches:External Output) |
| Method |
Membrane switch |
| Mechanical Life |
1 million times or more |
| Emergency Stop Switch |
Method |
Push-lock type (contact b, dual-circuit)
|
| Mechanical Life |
100,000 times or more |
| Rated Voltage |
24V DC |
| Rated Current |
1A(load resistance) |
| Key Switch |
Number of Contacts |
Contact a, single-circuit
|
| Mechanical Life |
250,000 times or more |
| Electrical Life |
100,000 times or more(switching frequency: 1,200 times/hour) |
Deadman Switch (3-position) |
Method |
3-position (contact a, dual-circuit*)
|
| Mechanical Life |
OFF → ON: One million times or more OFF → ON → OFF: 100,000 times or more |
| Rated Voltage |
24V DC |
| Rated Current |
1A(load resistance) |
Deadman Switch (Momentary) |
Method |
Momentary
|
| Mechanical Life |
1 million times or more |
| External interface |
TB2(Terminal Block) |
RS-232C, Asynchronous type, Data length : 7,8 bits,
Parity : even, odd, none, Stop bit : 1,2 bits,
Baud rate : 4800, 9600, 19200, 38400, 57600, 76800, 115200bps
|
| TB3(Terminal Block) |
RS-422/485, Asynchronous type, Data length : 7,8 bits, Parity : even, odd, none, Stop bit : 1,2 bits, Baud rate : 4800, 9600, 19200, 38400, 57600, 76800, 115200, 187500 *3bps |
| CF card interface |
Compatible with CompactFlashTM |
| Ethernet |
Complies with IEEE802.3 Baud rate: 10Mbps, 100Mbps Cable: 100Ω Unsealed twist pair, Category 5, Max length: 100m |
- |
| USB |
Type A, Type B (Ver1.1) |
| Clock & Back up memory |
Battery |
Coin-type lithium primary battery |
| Back up memory(SRAM) |
512KB |
128KB |
| Back up period |
5 years (Ambient temperature 25°C) |
| Calendar accuracy |
Gap±90 sec. per month (Ambient temperature 25°C) |
|